Document IIF
Comparaison de l'expérience et de la simulation CFD dans le système de pompe à chaleur utilisant un thermoaccumulateur et un cycle à éjecteur pour le chauffage des locaux et l’entreposage frigorifique.
The comparison of experiment and CFD simulation in the heat pump system using thermobank and ejector cycle for heating room and cold storage.
Numéro : pap. 47
Auteurs : LE NGOC C., CHOI K. II, OH J. T.
Résumé
This paper compares the CFD simulation and experimental results of the COS (condenser outlet split), DOS (diffuser outlet split) ejector refrigeration cycle with a standard ejector cycle. The system is investigated experimentally and CFD simulated under thermobank. The dimension L×W×H of cold storage is 3×1,6×1,4 m, thermobank is 600×300×400mm.The two phase ejector is used in system which the purpose increases in coefficient of performance (COP) and decrease in compressor displacement relative to a standard vapour compressor cycle.Nozzle with different Dnt and the adjustable ejector were also studied under different
conditions.The results ofCFD simulation showed that Dnt(diameter of motive nozzle) of 1mm and Dnm(diameter of mixing chamber) of 6mm yielded the best ejector efficiency and energy efficiency ratio. The COS and DOS ejector cycle are advantageous because of offering the potential for more than one evaporation temperature and it also do not include a liquid - vapour separator. When compared to standard cycle, the heat pump system using COS or DOS ejector cycle got maximum COP improvements of 24.5%
with experimental results.
Documents disponibles
Format PDF
Pages : 13
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : The comparison of experiment and CFD simulation in the heat pump system using thermobank and ejector cycle for heating room and cold storage.
- Identifiant de la fiche : 30023400
- Langues : Anglais
- Source : 5th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Beijing, Chine, 6-8 avril 2018
- Date d'édition : 06/04/2018
- DOI : http://dx.doi.org/10.18462/iir.iccc.2018.0047
Liens
Voir d'autres communications du même compte rendu (72)
Voir le compte rendu de la conférence
-
CFD simulation and experimental investigation p...
- Auteurs : LE NGOC C., CHOI G. I., OH J. T.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche
-
The comparison of experiment results and CFD si...
- Auteurs : LE NGOC C., CHOI G. I., OH J. T., et al.
- Date : 07/04/2016
- Langues : Anglais
- Source : 4th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Auckland, New Zealand, April 7-9, 2016.
- Formats : PDF
Voir la fiche
-
Experimental investigation and simulation proce...
- Auteurs : LE N. C., OH J. T.
- Date : 23/06/2014
- Langues : Anglais
- Source : 3rd IIR International Conference on Sustainability and the Cold Chain. Proceedings: London, UK, June 23-25, 2014
- Formats : PDF
Voir la fiche
-
Simulación e investigación experimental del sis...
- Auteurs : LE N. C., OH J. T.
- Date : 11/2016
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - n. 496
- Formats : PDF
Voir la fiche
-
Numerical [study] and simulation on nozzle para...
- Auteurs : LE NGOC C., CHOI G. I., OH J. T.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche