Un nouveau concept de pompe décentralisée pour un système frigorifique indirect.
A novel decentralised pump concept for indirect refrigeration system.
Auteurs : ROGSTAM J., CAI Z.
Résumé
Supermarkets are intensive users of energy in most countries. Electricity consumption in large supermarkets in US and France is estimated to 4% of the national electric energy use. The electrical energy used in the Swedish supermarkets account for 3% (1.8 TWh) of the annual national electricity consumption. The refrigeration system in the supermarket accounts for about 40% of the electricity used. Thus, there is a potential to save energy consumption in this field. This study has focus on the indirect supermarket refrigeration system and specifically the energy saving potential of the distribution energy. A novel concept of decentralised pumps in indirect refrigeration systems has been theoretically and experimentally evaluated. A miniature supermarket with refrigeration system was installed in a laboratory with controlled indoor conditions. The system was well instrumented to measure the required system parameters. Three steps were taken in the evaluation. The first step was to test different fixed pump speed conditions, followed by two controlled pump speed conditions; the last step was the decentralised pump concept. Through these 3 steps the energy saving of the refrigeration system was evaluated. When comparing the reference central pump concept and the decentralised pump system, the required pump energy was decreased by 17%. The total energy consumption of the system was decreased by 6%. Thus, the decentralised pump system has a large potential for saving the energy. The central pump was not properly sized and a calculation shows that with a proper size and efficiency the saving figure of the total pump energy would be 34% and the system energy saving 9%. Further improvements of the system are proposed and discussed to make the indirect refrigeration system even more efficient i.e. reducing the parasite losses.
Documents disponibles
Format PDF
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A novel decentralised pump concept for indirect refrigeration system.
- Identifiant de la fiche : 2011-0230
- Langues : Anglais
- Source : IIR/Eurotherm sustainable refrigeration and heat pump technology conference. Proceedings of the Eurotherm Seminar No. 88, Stockholm, Sweden, June 13-16, 2010.
- Date d'édition : 13/06/2010
Liens
Voir d'autres communications du même compte rendu (49)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Systèmes frigorifiques indirects;
Supermarchés, meubles de vente;
Efficacité energétique, économie d'énergie - Mots-clés : Système frigorifique; Consommation d'énergie; Comparaison; Calcul; Meuble de vente; Conception; Supermarché; Pompe; Experimentation; Efficacité énergétique; Économie d'energie
-
Misurazione dei rendimenti degli impianti a CO2...
- Auteurs : ZOUGHAIB A., BORLEIN C., CLODIC D.
- Date : 2008
- Langues : Italien
- Source : IIF-IIR/Ind. Form. - vol. 32 - n. 6
Voir la fiche
-
Recent refrigeration equipment trends in superm...
- Auteurs : LUNDQVIST P. G.
- Date : 2000
- Langues : Français
- Source : Bull. IIF-IIR - vol. 80 - n. 5
Voir la fiche
-
Tendencia de los equipos frigoríficos de los su...
- Auteurs : LUNDQVIST P. G.
- Date : 01/2002
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 30 - n. 333
Voir la fiche
-
Najnowsze trendy w urzadzeniach chlodniczych su...
- Auteurs : LUNDQVIST P. G.
- Date : 2000
- Langues : Polonais
- Source : Chlodnictwo - vol. 35 - n. 11
Voir la fiche
-
Promotion of energy efficient display cabinets.
- Auteurs : AXELL M., FAHLÉN P. O.
- Date : 1999
- Langues : Anglais
- Source : Refrigerated Transport, Storage and Retail Display.
- Formats : PDF
Voir la fiche