Performance de chauffage et de refroidissement d’un système de pompe à chaleur géothermique miniature.
Heating and cooling performance of a minitype ground source heat pump system.
Auteurs : ZHAI X. Q., CHENG X. W., WANG R. Z.
Type d'article : Article, Étude de cas
Résumé
A minitype ground source heat pump (GSHP) system was designed and installed in the green energy building of Shanghai Jiao Tong University for the purpose of satisfying the thermal environment of a meeting room with the covered area of 180 m2. The rated cooling capacity of the heat pump is 22.3 kW with the electricity consumption of 5.3 kW. Correspondingly, the rated heating capacity and electricity consumption in heating mode is 29.5 kW and 6.9 kW, respectively. The ground heat exchanger consists of 9 vertical boreholes. There is a single U-tube with the diameter of 32 mm in each borehole. The whole length of the U-tube is 580 m. The experimental investigation was carried out in both cooling mode and heating mode. After one year, the average temperature of soil was about 18 °C, which is nearly the same as the original soil temperature. The experimental results are instructive to the design and operation of GSHP systems in Shanghai and other cities with similar climatic feature.
Détails
- Titre original : Heating and cooling performance of a minitype ground source heat pump system.
- Identifiant de la fiche : 30020945
- Langues : Anglais
- Sujet : Environnement
- Source : Applied Thermal Engineering - vol. 111
- Date d'édition : 25/01/2017
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2016.03.117
Liens
Voir d'autres articles du même numéro (32)
Voir la source
Indexation
-
On field performances of geothermal heat pumps:...
- Auteurs : BAZZOCCHI F., CROCI L.
- Date : 02/2014
- Langues : Anglais
- Source : 49th AiCARR International Conference. Historical and existing buildings: designing the retrofit. An overview from energy performances to indoor air quality.
- Formats : PDF
Voir la fiche
-
Ispitivanje karakteristika sistema i rekonstruk...
- Auteurs : CUI P., AN H., JIANG H.
- Date : 12/2016
- Langues : Anglais
- Source : 47th International HVAC&R Congress and Exhibition.
- Formats : PDF
Voir la fiche
-
Conception d'un système à pompe à chaleur à sou...
- Auteurs : WU L., YE D., LIANG T., et al.
- Date : 06/2008
- Langues : Chinois
- Source : HV & AC - vol. 38 - n. 6
- Formats : PDF
Voir la fiche
-
Solar energy for buildings: clean energies util...
- Auteurs : OMER A. M.
- Date : 18/09/2012
- Langues : Anglais
- Source : EuroSun 2012: solar energy for a brighter future. ISES-Europe solar conference. Conference proceedings: Rijeka, Croatia, 18-20 September 2012.
- Formats : PDF
Voir la fiche
-
Control of Heat Transfer in a Vertical Ground H...
- Auteurs : SALHEIN K., KOBUS C. J., ZOHDY M.
- Date : 07/2022
- Langues : Anglais
- Source : Energies - 15 - 14
- Formats : PDF
Voir la fiche