Étude expérimentale sur l’utilisation du R-22, du R-427A, du R-161 et du R-290 dans une pompe à chaleur aérothermique pour le chauffage de locaux à températures ambiantes basses.
Experimental study on R-22, R-427A, R-161 and R-290 in air-source heat pump for space heating at low ambient temperatures.
Résumé
To help reduce the warming impacts, this study evaluates the drop-in performances of R-427A, R-161 and R-290 in R-22 air source heat pump with EVI (Economized Vapor Injection). The results show that the IPLV(H) of R-161 and R-290 arises 5~8% relative to R-22 with EVI on. A reversal occurs between R-290 and the baseline with EVI on, making the IPLV(H) of R-290 superior to that of R-22 by 3.6~5.2% from worse performance with EVI off. At -20/41°C condition, the capacity and COP of R-290 increase by 38% and 19%, respectively. Considering COP and discharge temperatures, R-290 is better-performed to replace R-22 in high pressure ratio conditions. Based on LCCP (Life Cycle Climate Performance) model, 11% of the equivalent CO2 emission can be reduced by using R-161 and R-290. However, the discharge temperature of R-161 is high in the high pressure ratio condition. R-290 is the most synthetically beneficial alternative.
Documents disponibles
Format PDF
Pages : 147-154
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental study on R-22, R-427A, R-161 and R-290 in air-source heat pump for space heating at low ambient temperatures.
- Identifiant de la fiche : 30025236
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 96
- Date d'édition : 12/2018
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2018.08.021
Liens
Voir d'autres articles du même numéro (20)
Voir la source
Indexation
-
Thèmes :
HCFC;
Pompes à chaleur à usage domestique;
HFC;
Hydrocarbures - Mots-clés : R161; Comparaison; Système aérothermique; R290; R22; Substitut; Pompe à chaleur; Performance; R427a
-
Experimental study on the performance of R290 a...
- Auteurs : LEI B., SHI H., WANG C., WU J., ZHANG L.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
Performance of Care-50 as an R22 replacement in...
- Auteurs : FIRTH A., CARRINGTON G.
- Date : 19/09/1999
- Langues : Anglais
- Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
- Formats : PDF
Voir la fiche
-
Energy comsumption and TEWI comparison of R410A...
- Auteurs : FELDMAN S. J., SPATZ M. W.
- Date : 23/10/1995
- Langues : Anglais
- Source : Stratospheric Ozone Protection for the 90's. 1995 International CFC and Halon Alternatives Conference & Exhibition. Conference proceedings.
Voir la fiche
-
Investigation of R-290/R-170 substituting R-22/...
- Auteurs : XIE Y. B., LIU C. T., LUN L. Y., et al.
- Date : 05/04/2008
- Langues : Anglais
- Source : Cryogenics and refrigeration. Proceedings of ICCR'2008.
Voir la fiche
-
Comparing R290 with R22 in heat pumps.
- Auteurs : HWANG Y., GADO A., RADERMACHER R.
- Date : 01/2003
- Langues : Anglais
- Source : ASHRAE Journal - vol. 45 - n. 1
Voir la fiche