Résumé
This paper described the optimization of the operation conditions for CO2 heat pump, which produces hot tap water and ice water for a dairy factory. The analysis revealed that the volume of the storage tank for hot water accumulation was not sufficient. This led to discontinuous operation of the heat pump and to excessive use of district heating. The optimum storage tank of 3.0 m3 provided 1.9 % of energy savings and continuous work of the system. The gas cooler performance at different gas cooler pressures and different compressor frequency were evaluated. Optimum gas cooler pressure, which refers to the highest COP, was found to be in the range between 95.6 and 99.9 bars depending on frequency of the compressor’s motor. This provided the gas cooler performance in the range between 82.6 and 167.5 kW. The optimum COP of the system was in the range between 3.59 and 3.54.
Documents disponibles
Format PDF
Pages : 7 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Optimized operation conditions for CO2 heat pump for chilling of ice water/heating of hot tap water to 80°C.
- Identifiant de la fiche : 30012407
- Langues : Anglais
- Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
- Date d'édition : 02/08/2014
Liens
Voir d'autres communications du même compte rendu (119)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Pompes à chaleur à usage industriel;
CO2 - Mots-clés : Eau chaude; R744; Pompe à chaleur; Performance; Optimisation; Laiterie; COP; Frigorigène; CO2
-
Performance evaluation of high-temperature heat...
- Auteurs : REN S., AHRENS M. U., HAFNER A., WIDELL K. N.
- Date : 13/06/2022
- Langues : Anglais
- Source : 15th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2022). Proceedings. Trondheim, Norway, June 13-15th 2022.
- Formats : PDF
Voir la fiche
-
Feasibility study of various conventional and u...
- Auteurs : YOUNG J., SUBIANTORO A.
- Date : 07/12/2020
- Langues : Anglais
- Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
- Formats : PDF
Voir la fiche
-
Etude sur l'évaluation de la performance d'un s...
- Auteurs : HAMADA Y., MURAKAWA S., AMAZAWA K., et al.
- Date : 08/2011
- Langues : Japonais
- Source : Transactions of the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan - n. 173
Voir la fiche
-
Performance analysis of a CO2 heat pump water h...
- Auteurs : YOKOYAMA R., KOHNO Y., WAKUI T., et al.
- Date : 07/06/2010
- Langues : Anglais
- Source : ACRA2010. Asian conference on refrigeration and air conditioning: Tokyo, Japan, June 7-9, 2010.
- Formats : PDF
Voir la fiche
-
Development of a commercial heat pump water hea...
- Auteurs : YU P. Y., YANG C. C., NIAN S. H., et al.
- Date : 07/06/2010
- Langues : Anglais
- Source : ACRA2010. Asian conference on refrigeration and air conditioning: Tokyo, Japan, June 7-9, 2010.
- Formats : PDF
Voir la fiche